Voltage Drop Calculator
Use the free Voltage Drop Calculator on AixKit to get instant, accurate results in your browser. No sign-up or installation required.
Use the free Voltage Drop Calculator on AixKit to get instant, accurate results in your browser. No sign-up or installation required.
This tool calculates voltage drop across a cable run using conductor material (copper or aluminum), AWG wire size, one-way run length, current, system voltage (120–480 V), and phase (single or three-phase). The result shows drop in volts, drop as a percentage of supply voltage, voltage delivered at the load, and a pass/fail check against NEC 3% and 5% thresholds.
This is different from the Ohm's Law Calculator, which solves the general V = IR relationship between any three variables. This page is scoped to conductor runs: it uses tabulated AWG resistivity data, accounts for round-trip conductor length, and cross-references the result against NEC recommendations.
Voltage drop is the reduction in electrical potential between two points caused by conductor resistance. In a zero-resistance conductor there would be no drop — every volt at the source would arrive at the load. In practice, all conductors resist current, and that resistance produces a proportional voltage loss.
How significant the drop is depends entirely on the load. A 2% drop on a long lighting branch is inconsequential. A 4% drop supplying a variable-frequency drive, PLC, or low-voltage control circuit may trigger mis-operation, reduced motor torque, or equipment fault.
The National Electrical Code (NEC) includes informational notes recommending:
These are recommendations, not enforceable violations — but most engineers treat them as design targets. Exceeding 5% combined drop is a signal to upsize wire, shorten the run, or split the load. Voltage-sensitive equipment (VFDs, PLCs, solenoid valves, low-voltage systems) often has tighter internal tolerances (±5–10% of rated voltage), so staying well within the 3% limit is the practical goal on those circuits.
Example 1 — Short residential branch circuit:
12 AWG copper • 25 ft run • 15 A • 120 V single-phase
Round-trip: 50 ft → R = 1.93 × 50 ÷ 1000 = 0.0965 Ω → V_drop = 15 × 0.0965 = 1.45 V (1.2%) → PASS
Short residential branch circuits at typical loads stay well within limits on 12 AWG.
Example 2 — Long 240 V feeder:
2 AWG copper • 150 ft run • 60 A • 240 V single-phase
Round-trip: 300 ft → R = 0.191 × 300 ÷ 1000 = 0.0573 Ω → V_drop = 60 × 0.0573 = 3.44 V (1.4%) → PASS
Higher system voltage absorbs the drop effectively. 2 AWG handles 60 A over 150 ft on 240 V with margin.
Example 3 — Long 120 V circuit where drop is too high:
14 AWG copper • 100 ft run • 20 A • 120 V single-phase
Round-trip: 200 ft → R = 3.07 × 200 ÷ 1000 = 0.614 Ω → V_drop = 20 × 0.614 = 12.28 V (10.2%) → FAIL
Fix: upsize to 8 AWG (0.764 Ω/1000 ft). R = 0.153 Ω → V_drop = 3.06 V (2.5%) → PASS.
This calculator uses tabulated DC resistivity values from NEC tables at 20°C. Actual measured drop may differ because: