Voltage Drop Calculator

Part of: Engineering →


Voltage Drop Calculator

Distance from panel to load (one-way)
Please enter valid wire length and current values.

Voltage Drop Analysis

How to Use the Voltage Drop Calculator

  1. Select Conductor Material (Copper or Aluminum) and Wire Size from the AWG dropdown.
  2. Enter One-Way Wire Length in feet (the distance from panel to load) and Current in amps.
  3. Select System Voltage (120 V to 480 V) and Phase (single or three-phase).
  4. Click Calculate to see voltage drop, drop percentage, voltage at load, wire resistance, and NEC pass/fail status.

What This Calculator Does

This tool calculates voltage drop across a cable run using conductor material (copper or aluminum), AWG wire size, one-way run length, current, system voltage (120–480 V), and phase (single or three-phase). The result shows drop in volts, drop as a percentage of supply voltage, voltage delivered at the load, and a pass/fail check against NEC 3% and 5% thresholds.

This is different from the Ohm's Law Calculator, which solves the general V = IR relationship between any three variables. This page is scoped to conductor runs: it uses tabulated AWG resistivity data, accounts for round-trip conductor length, and cross-references the result against NEC recommendations.

What Voltage Drop Means in a Real Circuit

Voltage drop is the reduction in electrical potential between two points caused by conductor resistance. In a zero-resistance conductor there would be no drop — every volt at the source would arrive at the load. In practice, all conductors resist current, and that resistance produces a proportional voltage loss.

How significant the drop is depends entirely on the load. A 2% drop on a long lighting branch is inconsequential. A 4% drop supplying a variable-frequency drive, PLC, or low-voltage control circuit may trigger mis-operation, reduced motor torque, or equipment fault.

How Each Input Affects the Result

NEC Limits and When Drop Becomes a Problem

The National Electrical Code (NEC) includes informational notes recommending:

These are recommendations, not enforceable violations — but most engineers treat them as design targets. Exceeding 5% combined drop is a signal to upsize wire, shorten the run, or split the load. Voltage-sensitive equipment (VFDs, PLCs, solenoid valves, low-voltage systems) often has tighter internal tolerances (±5–10% of rated voltage), so staying well within the 3% limit is the practical goal on those circuits.

Worked Examples

Example 1 — Short residential branch circuit:
12 AWG copper • 25 ft run • 15 A • 120 V single-phase
Round-trip: 50 ft → R = 1.93 × 50 ÷ 1000 = 0.0965 Ω → V_drop = 15 × 0.0965 = 1.45 V (1.2%) → PASS
Short residential branch circuits at typical loads stay well within limits on 12 AWG.

Example 2 — Long 240 V feeder:
2 AWG copper • 150 ft run • 60 A • 240 V single-phase
Round-trip: 300 ft → R = 0.191 × 300 ÷ 1000 = 0.0573 Ω → V_drop = 60 × 0.0573 = 3.44 V (1.4%) → PASS
Higher system voltage absorbs the drop effectively. 2 AWG handles 60 A over 150 ft on 240 V with margin.

Example 3 — Long 120 V circuit where drop is too high:
14 AWG copper • 100 ft run • 20 A • 120 V single-phase
Round-trip: 200 ft → R = 3.07 × 200 ÷ 1000 = 0.614 Ω → V_drop = 20 × 0.614 = 12.28 V (10.2%) → FAIL
Fix: upsize to 8 AWG (0.764 Ω/1000 ft). R = 0.153 Ω → V_drop = 3.06 V (2.5%) → PASS.

How to Reduce Voltage Drop

Important Limitations

This calculator uses tabulated DC resistivity values from NEC tables at 20°C. Actual measured drop may differ because:

Frequently Asked Questions